Refrigeration Preventive Maintenance Checklist
A printable commercial refrigeration PM checklist with readings, condensing unit, evaporator and leak checks. Add your logo, print or save as PDF.
How to use| Item | OK | Needs attention | N/A | Notes |
|---|---|---|---|---|
| Readings | ||||
| Box / case temp: design ( °F) / actual ( °F) | ||||
| Suction pressure ( psig) / sat. temp ( °F) | ||||
| Discharge pressure ( psig) / sat. temp ( °F) | ||||
| Superheat ( °F) / subcooling ( °F) | ||||
| Compressor amps ( A) / RLA ( A) | ||||
| Supply voltage ( V) / ambient temp ( °F) | ||||
| Defrosts per day () / fail-safe ( min) | ||||
| Condensing unit | ||||
| Condenser coil cleaned | ||||
| Condenser fan motors and blades OK | ||||
| Compressor: no abnormal noise, vibration or oil | ||||
| Crankcase heater working | ||||
| Contactors and connections OK | ||||
| Sight glass / moisture indicator OK | ||||
| Filter drier: no temperature drop across it | ||||
| Head pressure control / fan cycling OK | ||||
| High / low pressure safeties tested | ||||
| Evaporator | ||||
| Coil clean, no ice | ||||
| Fans running, blades clean | ||||
| Drain line and drain heater OK | ||||
| Defrost heaters and termination tested | ||||
| TXV bulb secure and insulated | ||||
| General | ||||
| Leak check (method ) | ||||
| Line insulation intact | ||||
| Door gaskets and heaters OK | ||||
| Temperature alarm / monitoring working | ||||
| Refrigerant added ( lb) recorded | ||||
How to use
- The refrigeration PM template is already loaded, with readings, condensing unit, evaporator and general sections.
- Add your business name, logo and the job details, or leave them blank to fill in by hand.
- Edit, add, remove or move items and sections. The preview updates as you type.
- Press Print, or Save as PDF and choose “Save as PDF” in the print window.
- Save a draft to reuse the same checklist on your next job.
About this refrigeration PM checklist
Use it as a general commercial refrigeration maintenance checklist for coolers, freezers, prep tables and other systems. Record box temperature, suction and discharge pressures, superheat, subcooling, amps and defrost settings, then tick each check.
Refrigeration PM by frequency
The printed sheet follows the system: readings, condensing unit, evaporator, then general checks. This is how that work usually splits by interval. Kitchens with grease and flour dust need it more often than a clean storeroom; follow the manufacturer and your service agreement.
| Check | Why it matters |
|---|---|
| Box or case temperature, design vs actual | The number the customer cares about. A drift up is often the first sign of a coil, fan or charge problem. |
| Suction and discharge pressures, superheat and subcooling | Together they tell you about charge, metering device and condenser performance. Recording them lets you see a trend. |
| Clean the condenser coil | A dirty condenser is the most common cause of high head pressure and compressor strain on commercial units. |
| Evaporator coil clear of ice, fans running | Ice or a failed fan starves the coil and the box warms up. |
| Drain line and drain heater | A frozen or blocked drain on a freezer turns into an ice block on the floor or in the coil. |
| Door gaskets and heaters | Torn gaskets let in warm, wet air, which means more frost and more defrosts. |
| Check | Why it matters |
|---|---|
| Test defrost heaters and termination | A failed heater or termination switch leaves a coil iced or overheating the box. |
| Check defrosts per day and fail-safe time | Too few defrosts ice the coil; too many waste energy and warm the product. |
| Test high and low pressure safeties | They protect the compressor and are often not tested until they fail. |
| Check compressor amps against RLA, and the crankcase heater | High amps or a failed heater warn of compressor trouble before it fails. |
| Leak check and record any refrigerant added | Required records for many systems, and the only way to show a leak rate. |
| Test the temperature alarm or monitoring | An alarm that does not work is how stock gets lost overnight. |
Print one sheet per system. There is an optional Refrigerant box in Step 2 so the refrigerant type prints in the header.
What's on the sheet
26 lines in four sections. Readings has write-in blanks for box or case temperature (design and actual), suction and discharge pressure with their saturation temperatures, superheat and subcooling, compressor amps against RLA, supply voltage and ambient temperature, and defrosts per day with the fail-safe time. Condensing unit covers the condenser coil, condenser fans, the compressor (noise, vibration, oil), the crankcase heater, contactors and connections, the sight glass, the filter drier, head pressure control and the high and low pressure safeties. Evaporator covers the coil, fans, drain line and drain heater, defrost heaters and termination, and the TXV bulb. General covers the leak check (with the method written in), line insulation, door gaskets and heaters, the temperature alarm, and any refrigerant added.
The Units buttons above the sheet switch the blanks between °F and °C and between PSI and kPa before you print.
Getting a PDF copy
Fill in the job details and your business name first. Then press Save as PDF. Your browser opens its print window, and you pick “Save as PDF” as the printer. The paper setting switches between US Letter and A4. Your business details and logo are saved on your own device only, so the next sheet is quicker.
Using it as a refrigeration PM program
Keep the filled sheets for each system in date order. The readings are the useful part over time. A suction pressure that keeps drifting, amps creeping toward RLA, or refrigerant added on more than one visit is what tells you a repair is coming, and the earlier sheets are your evidence when you quote it. Copy the service intervals from the equipment manual and your service agreement into the notes so the next tech knows what is due.
This sheet or the walk-in cooler checklist?
This one is a general PM sheet for any commercial system. The walk-in cooler checklist adds box-specific items like door closers and panels. For single cabinets use the reach-in refrigerator checklist, for open and glass-door cases the display case checklist, and for ice machines the ice machine cleaning checklist.
A starting point, not a manufacturer or code requirement. Follow the equipment manufacturer, your service agreement and the EPA rules that apply to the system.
Questions
What does a commercial refrigeration PM include?
Temperature and pressure readings, superheat and subcooling, amps and voltage, condenser and evaporator cleaning, fans, defrost, drains, safeties, a leak check and alarm testing.
Should I record refrigerant added?
Yes. EPA rules under Section 608 and the AIM Act set leak repair and record-keeping requirements for many commercial systems, depending on refrigerant type and charge size. Recording the amount added on every visit helps you keep those records.
How often should commercial refrigeration be serviced?
Quarterly PM is common, and monthly in harsh kitchen environments. Follow the manufacturer and your service agreement.