Refrigeration Preventive Maintenance Checklist

A printable commercial refrigeration PM checklist with readings, condensing unit, evaporator and leak checks. Add your logo, print or save as PDF.

How to use

Step 1 Pick a template

Want to customize this checklist or mix trades? Use the custom builder

Step 2 Add your details (optional)

Your business
Logo

Saved on this device only, never uploaded.

Job

Step 3 Edit the checklist

Step 4 Print or save as PDF

More checklists

Make your own checklist

How to use

  1. The refrigeration PM template is already loaded, with readings, condensing unit, evaporator and general sections.
  2. Add your business name, logo and the job details, or leave them blank to fill in by hand.
  3. Edit, add, remove or move items and sections. The preview updates as you type.
  4. Press Print, or Save as PDF and choose “Save as PDF” in the print window.
  5. Save a draft to reuse the same checklist on your next job.

Back to top ↑

About this refrigeration PM checklist

Use it as a general commercial refrigeration maintenance checklist for coolers, freezers, prep tables and other systems. Record box temperature, suction and discharge pressures, superheat, subcooling, amps and defrost settings, then tick each check.

Refrigeration PM by frequency

The printed sheet follows the system: readings, condensing unit, evaporator, then general checks. This is how that work usually splits by interval. Kitchens with grease and flour dust need it more often than a clean storeroom; follow the manufacturer and your service agreement.

Every PM visit
CheckWhy it matters
Box or case temperature, design vs actualThe number the customer cares about. A drift up is often the first sign of a coil, fan or charge problem.
Suction and discharge pressures, superheat and subcoolingTogether they tell you about charge, metering device and condenser performance. Recording them lets you see a trend.
Clean the condenser coilA dirty condenser is the most common cause of high head pressure and compressor strain on commercial units.
Evaporator coil clear of ice, fans runningIce or a failed fan starves the coil and the box warms up.
Drain line and drain heaterA frozen or blocked drain on a freezer turns into an ice block on the floor or in the coil.
Door gaskets and heatersTorn gaskets let in warm, wet air, which means more frost and more defrosts.
Quarterly or yearly
CheckWhy it matters
Test defrost heaters and terminationA failed heater or termination switch leaves a coil iced or overheating the box.
Check defrosts per day and fail-safe timeToo few defrosts ice the coil; too many waste energy and warm the product.
Test high and low pressure safetiesThey protect the compressor and are often not tested until they fail.
Check compressor amps against RLA, and the crankcase heaterHigh amps or a failed heater warn of compressor trouble before it fails.
Leak check and record any refrigerant addedRequired records for many systems, and the only way to show a leak rate.
Test the temperature alarm or monitoringAn alarm that does not work is how stock gets lost overnight.

Print one sheet per system. There is an optional Refrigerant box in Step 2 so the refrigerant type prints in the header.

What's on the sheet

26 lines in four sections. Readings has write-in blanks for box or case temperature (design and actual), suction and discharge pressure with their saturation temperatures, superheat and subcooling, compressor amps against RLA, supply voltage and ambient temperature, and defrosts per day with the fail-safe time. Condensing unit covers the condenser coil, condenser fans, the compressor (noise, vibration, oil), the crankcase heater, contactors and connections, the sight glass, the filter drier, head pressure control and the high and low pressure safeties. Evaporator covers the coil, fans, drain line and drain heater, defrost heaters and termination, and the TXV bulb. General covers the leak check (with the method written in), line insulation, door gaskets and heaters, the temperature alarm, and any refrigerant added.

The Units buttons above the sheet switch the blanks between °F and °C and between PSI and kPa before you print.

Getting a PDF copy

Fill in the job details and your business name first. Then press Save as PDF. Your browser opens its print window, and you pick “Save as PDF” as the printer. The paper setting switches between US Letter and A4. Your business details and logo are saved on your own device only, so the next sheet is quicker.

Using it as a refrigeration PM program

Keep the filled sheets for each system in date order. The readings are the useful part over time. A suction pressure that keeps drifting, amps creeping toward RLA, or refrigerant added on more than one visit is what tells you a repair is coming, and the earlier sheets are your evidence when you quote it. Copy the service intervals from the equipment manual and your service agreement into the notes so the next tech knows what is due.

This sheet or the walk-in cooler checklist?

This one is a general PM sheet for any commercial system. The walk-in cooler checklist adds box-specific items like door closers and panels. For single cabinets use the reach-in refrigerator checklist, for open and glass-door cases the display case checklist, and for ice machines the ice machine cleaning checklist.

A starting point, not a manufacturer or code requirement. Follow the equipment manufacturer, your service agreement and the EPA rules that apply to the system.

Questions

What does a commercial refrigeration PM include?

Temperature and pressure readings, superheat and subcooling, amps and voltage, condenser and evaporator cleaning, fans, defrost, drains, safeties, a leak check and alarm testing.

Should I record refrigerant added?

Yes. EPA rules under Section 608 and the AIM Act set leak repair and record-keeping requirements for many commercial systems, depending on refrigerant type and charge size. Recording the amount added on every visit helps you keep those records.

How often should commercial refrigeration be serviced?

Quarterly PM is common, and monthly in harsh kitchen environments. Follow the manufacturer and your service agreement.